Primian-2™ SmartStart Modules
Cells 2 3 4 5
Module 5 pole ballast switching, with 30 seconds cathode heating
Standard S2C S3C S4C S5C
AutoTest® 3 hour AS2C/D/P AS3C/D/P AS4C/D/P AS5C/D/P
AutoTest® 1 hour AS2C/M1/D/P AS3C/M1/D/P AS4C/M1/D/P AS5C/M1/D/P
Case Type Ap 30 mm Ap 30 mm Ap 30 mm Ap 30 mm
Lamp Watts Figures quoted are ballast lumen factors, %
T5 4  38 27 34  59  
6  28* 30 36  59  
8  27* 30 35  63  
13   19* 35  33*  
14   15* 26  26*  
21     18* 24*  
T5C 22     15  20*  
T8 18   31  17*
36     10*  14*
58      
70      
SEL 5 34  26 30  44    
7 23*  24 30  51    
9  32 36  54    
11  22* 24  32*    
DEL 10 12  26  55    
13  26* 27  32*    
18   16  22*    
26   18*  21*    
TEL 13   10  28*    
18   20  22*    
26   14* 22*    
32        
TC-L 18 15 18  29    
24   14  18*    
34   15*      
36  11*  17*    
40        
2D 16 18* 21  30*    
21   23*  31*    
28   14* 19*    
38     16*      
55     9*    
F 18  13 16  25    
24  10* 18  17*    
36   9*  16*    
Data also applies to 1 hour duration modules
These modules are not suitable for remote mounting above 0.5m.
Where BLFs are entered in red or marked * - remove link