AutoTest 4 & 5 cell Modules
Cells 4 5
Module AutoTest AutoTest AutoTest
5 pole ballast switching AS480 AS484 AS540
Lamp Watts Figures quoted are ballast lumen factors, %
T5 4
6
8
13 27
14 20
21
T8 15/18 24
30/36 14*
T12 20
40
SEL 5
7
9
11 25
DEL 10
13
18 20*
26 18*
TEL 13
18 14 20*
26 17*
32
TC-L 18 30 17
24 14 16* 15
34 18* 13*
36 16* 12*
40 11*
2D 10
16 24
21 19 18*
28 16* 17*
38* 14*
F 18 18
24 12
36
* Do not use 38 watt 2D lamp in non maintained mode

These modules are not suitable for remote mounting above 0.5 m

These modules are suitable only for use with non-amalgam lamps
Where BLFs are entered in red or marked * - remove link

2 & 3 Cell Data
4 & 5 Cell Data
4 & 5 Cell AutoTest
FastStart Modules
High Efficiency Data
High Efficiency T8 Data
High Output Data
Large Lamp Data
T5 Lamp Data