| Primian-2 SmartStart
Modules |
| Cells |
2 |
3 |
4 |
5 |
|
|
|
| Module |
5 pole ballast switching,
with 30 seconds cathode heating |
|
|
| Standard |
S2C |
S3C |
S4C |
S5C |
S5C/40 |
|
|
|
AutoTest® 3 hour |
AS2C/D/P |
AS3C/D/P |
AS4C/D/P |
AS5C/D/P |
AS5C/40/D/P |
|
|
|
AutoTest® 1 hour |
AS2C/M1/D/P |
AS3C/M1/D/P |
AS4C/M1/D/P |
AS5C/M1/D/P |
AS5C/40/M1/D/P |
|
|
| Case Type |
Ap 30 mm |
Ap 30 mm |
Ap 30 mm |
Ap 30 mm |
Ap 30 mm |
|
|
| Lamp |
Watts |
Figures quoted are
ballast lumen factors, % |
| T5 |
 |
4 |
38 |
27 |
34 |
59 |
|
|
|
| 6 |
28* |
30 |
36 |
59 |
|
|
|
| 8 |
27* |
30 |
35 |
63 |
|
|
|
| 13 |
|
19* |
35 |
33* |
|
|
|
| 14 |
|
15* |
26 |
26* |
|
|
|
| 21 |
|
|
18* |
24* |
|
|
|
| T5C |
|
22 |
|
|
15* |
20* |
|
|
|
| T8 |
 |
18 |
|
|
16 |
17* |
|
|
|
| 36 |
|
|
10* |
14* |
|
|
|
| 58 |
|
|
|
|
|
|
|
| 70 |
|
|
|
|
|
|
|
| SEL |
 |
5 |
34 |
26 |
30 |
44 |
|
|
|
| 7 |
23* |
24 |
30 |
51 |
|
|
|
| 9 |
|
32 |
36 |
54 |
|
|
|
| 11 |
|
22* |
24 |
32* |
|
|
|
| DEL |
 |
10 |
|
22 |
26 |
55 |
|
|
|
| 13 |
|
26* |
27 |
32* |
|
|
|
| 18 |
|
|
16 |
22* |
|
|
|
| 26 |
|
|
18* |
21* |
|
|
|
| TEL |
 |
13 |
|
|
10 |
28* |
|
|
|
| 18 |
|
|
20 |
22* |
|
|
|
| 26 |
|
|
14* |
22* |
|
|
|
| 32 |
|
|
|
|
|
|
|
| TC-L |
 |
18 |
|
15 |
18 |
29 |
|
|
|
| 24 |
|
|
14 |
18* |
|
|
|
| 34 |
|
|
15* |
|
|
|
|
| 36 |
|
|
11* |
17* |
|
|
|
| 40 |
|
|
|
|
8* |
|
|
| 2D |
 |
16 |
|
18* |
21 |
30* |
|
|
|
| 21 |
|
23* |
31* |
|
|
|
| 28 |
|
14* |
19* |
|
|
|
| 38 |
|
|
|
14 |
|
|
| 55 |
|
|
|
9* |
|
|
|
| F |
 |
18 |
|
13 |
16 |
25 |
|
|
|
| 24 |
10* |
18 |
17* |
|
|
|
| 36 |
|
9* |
16* |
|
|
|
| Data also applies to 1
hour duration modules |
| These modules are not
suitable for remote mounting above
0.5m. |
| Where BLF's are entered in red