AutoTest® Standard
Modules
Automatically tests:
- For 5 minutes duration
monthly
- For 1 hour duration 6
monthly
- For 3 hours duration
annually
- Mains present and
connected
- Battery present and in
circuit
- Operation of battery
charger
- Operation of emergency
lamps
- Operation of emergency circuit
& module
|
The Mackwell Emergency Light AutoTest®
System is built into a selected range of emergency
lighting modules and routinely tests all the
fundamental aspects of the emergency lighting
luminaire, reporting status through the LED. The
unit complies with the draft CELMA specification
for Emergency Lighting Testing systems, and exceeds
its testing requirements.
A continuous green LED indication: specified for
AutoTest® emergency modules confirms:
- Mains present and connected
- Battery present and in circuit,
- Satisfactory operation of the battery
charger.
- A flashing green LED: indicates a faulty
lamp.
- The LED off: indicates a battery fault, or
lack of power connection.
The AutoTest® System goes into self test
mode automatically at a suitable time, the test
schedule commences within a period of 37 days of
commissioning. This is programmed into the modules
during manufacture to ensure that no more than 15%
of luminaires in an installation are on test in any
one day. After this period, tests will be carried
out on a 30 day time frame as required, at a period
of low risk, normally when the switched supply is
off. If a period of low risk does not arise within
7 days of the required test then the test will be
carried out immediately. A longer duration test
will be carried out every 6th and 12th test.
Three durations of test are provided. Monthly
the unit is activated for 5 minutes and the output
to the lamp tested at the start and finish; 6
monthly the test will be conducted for 1 hour, and
annually the test will be conducted for the full
duration of 3 hours.
User Reset Facility
To reset the LED after the fault condition has
been rectified, the user simply switches the
switched or unswitched supply ON/OFF twice within
10 seconds, either external to or within the
luminaire.
Test Report Status
After each monthly test, the memory status is
incremented by one. The current status is displayed
by the extinguishing of the LED each time the mains
is turned on. After a delay of 30 seconds the LED
extinguishes (in groups of three to facilitate
counting), to indicate the number of tests carried
out, and resets after each annual test. In this
way, users can be assured that essential monthly, 6
monthly and annual tests have been carried out, and
compile any supporting records that they may
require. For example, 7 extinguishes at switch on
followed by a steady LED indicates 6 previous
monthly tests have been executed, and the unit is
fully operational.
An audible
alarm
will sound should a fault condition be found
during a test. The alarm will sound for 3 seconds
every 30 minutes until the fault condition is
rectified and the unit reset.
Compatible with High Frequency Ballasts
The AutoTest® Modules are compatible with
all known high frequency ballasts, utilising 4 pole
change over relays, and incorporating ballast
disconnection to ensure that ballasts are powered
down during tests. This will enable them to be
reset as if they had been switched off.
AutoTest® luminaires should be left powered off
until the installation is finally commissioned.
Mackwell AutoTest® Module selection.
See Ballast Lumen Factors:
2 & 3
cell Autotest & Standard Modules (AS453,
AS454, AS478, AS482)
4 & 5
cell Standard Modules (SM480, SM484)
4
& 5 cell AutoTest Modules (AS480, AS484,
AS540)
3, 4 & 5
cell High Efficiency Modules (AS554, AS555,
AS556)
References (Maintained):
| AutoTest® Module |
AS554 |
AS555 |
AS556 |
AS478 |
AS480 |
AS484 |
AS540 |
AS482 |
-
|
| as Standard Module |
SM554 |
SM555 |
SM556 |
SM478 |
SM480 |
SM484 |
-
|
SM482 |
SM483 |
| Tube watts: |
18/36 |
58 |
70 |
16 |
28 |
38 |
18 - 40 |
8 |
8 |
| Cells |
3 |
4 |
5 |
3 |
4 |
5 |
5 |
2 |
3 |
References (Non-Maintained):
| AutoTest® Module |
AS453 |
AS454 |
| as Standard Module |
SM453 |
SM454 |
| Tube watts: |
8 |
8 |
| Cells |
2 |
3 |
Dimensions (mm)
|
Width |
Height |
Length |
Fixing Centres |
| (A Can Size) |
42 |
35 |
150 |
140 |
Specifications:
| Mains Input |
240 volt ±6% ~50/60Hz |
|
(Other voltages available) |
| Battery Charge Current |
Substantially constant current at 250mA
nominal |
| Battery Discharge Current: |
1.05A nominal |
| Temperature: |
60ºC at any temperature reference
point. |
| Weight |
245 grams |